Dustpile Apps
Practical conductor reference · Canada & U.S.

GENERATOR OUTPUT · FEEDERS · LEADS

Conductor Sizer

Select your generator load and installation details. Compare practical conductor sizes, flexible cable types, parallel runs, voltage drop, and estimated conduit fill.

1

Installation inputs

CEC ampacity basis: copper values use CEC Table 2 for up to three insulated conductors in raceway or cable. Aluminum values use the corresponding CEC Table 4 basis. Use the lowest temperature rating of the insulation and all terminations.
2

Conductor construction

CEC Table 5C adjustment: 3 conductors = 100% of the Table 2/Table 4 ampacity. This applies at four or more conductors in the same raceway or cable. Confirm which conductors must be counted for the actual installation.
General generator feeder in conduitCanada & U.S. · Medium flexibility

Single insulated conductors. Use the wet-location marking where required.

CALCULATION RESULTS

Size comparison

CEC Table 2 base values for copper, adjusted for the selected Table 5C conductor count. Ambient-temperature correction is not included. Use the selected terminal-temperature column.

Size per conductorTable 2/4 baseAdjusted eachParallel ampacityVoltage dropStatus
14 AWG202020 A19.2%Undersized
12 AWG252525 A12.1%Undersized
10 AWG353535 A7.6%Undersized
8 AWG505050 A4.8%Undersized
6 AWG656565 A3.1%Undersized
4 AWG858585 A1.9%Undersized
2 AWG115115115 A1.2%Meets target
1 AWG130130130 A1%Meets target
1/0 AWG150150150 A0.8%Meets target
2/0 AWG175175175 A0.6%Meets target
3/0 AWG200200200 A0.5%Meets target
4/0 AWG230230230 A0.4%Meets target
250 kcmil255255255 A0.3%Meets target
300 kcmil285285285 A0.3%Meets target
350 kcmil310310310 A0.2%Meets target
400 kcmil335335335 A0.2%Meets target
500 kcmil380380380 A0.2%Meets target
600 kcmil420420420 A0.1%Meets target
700 kcmil460460460 A0.1%Meets target
750 kcmil475475475 A0.1%Meets target

CONDUIT CHECK

Estimated conduit fill

Enter every insulated conductor or cable that will occupy the raceway. For a multi-conductor cable, use the manufacturer’s overall cable diameter, not the individual conductor diameter.

This uses 53% fill for one conductor, 31% for two, and 40% for three or more. It is a planning aid. Confirm the actual cable O.D., raceway type, conductor adjustment, pulling tension, bend radius, and the applicable code table.

Calculated occupied area0.566 in²Suggested minimum nominal conduit1-1/4 inBased on approximately 0.49 in outside diameter each and a 40% fill limit.

Common generator choices

  • RW90 / THHN / XHHW-2: standard conductors pulled in conduit.
  • DLO: excellent flexibility for generator output leads and vibration-prone routing.
  • TECK90 / MC: robust mechanical protection where conduit is undesirable.
  • SOOW: portable, flexible connections, not a default permanent feeder.

Before you release a drawing

  • Confirm the generator breaker and terminal temperature rating.
  • Apply Table 5A ambient correction where needed. Table 5C is included for the selected conductor count.
  • Size neutral and equipment bonding conductors separately.
  • Check voltage drop at starting and non-linear loads, not only full-load amps.

Code reference boundary

This tool is an engineering starting point for 60 Hz AC systems, not a stamped design or a substitute for the current Canadian Electrical Code, NEC, equipment instructions, or your authority having jurisdiction.

Reference basis: CEC Table 2 for copper and Table 4 for aluminum conductors in raceway or cable. The tool applies Table 5C factors: 1–3 = 100%, 4–6 = 80%, 7–24 = 70%, 25–42 = 60%, and 43+ = 50%.